Project Information
Structural Criteria & Design Basis
Engineer Review Checklist
Tick an item only after the responsible engineer has independently verified it. Ticks are attestations: they add no calculations, are saved with the project and are printed in the report.
1. Geometric Parameters
Displayed starting values are illustrative only. Replace them with verified project data before interpreting results.
L and B stay the total clear inside dimensions; the partition sits inside them. A full-height partition makes two separate compartments (design case: one compartment full, the other empty). A partial-height baffle leaves one common water body.
With the opening open, both sides keep the same level, so the one-sided full-depth load applies only if the opening can be closed. The solid wall piers carry the load of the opening width.
Measured outward from outer tank wall face
Underground embedment & soil parameters
Adds external soil, surcharge and groundwater pressure on the walls (empty-tank case), soil cover load on the roof, and soil weight in bearing. Groundwater uses the Groundwater head above base underside input in section 2 (required). Enter 0 for wind where the walls are fully buried and justified. Seismic earth-pressure increments are not computed: include them in the factored seismic wall inputs.
Lateral surcharge uses q above. The roof live/access load entered in section 2 should include any surcharge acting on the soil cover.
2. Material, Soil & Load Properties
Steps up in 25 mm increments (min. wall 200, base 200, roof 150 mm) until flexure, shear, crack control and roof deflection pass. Unticked members keep your manual value.
Propped applies only with a top cover slab. The roof and its wall connection must be detailed to carry the top reaction (shown in the calculation notes).
Clear cover must be greater than 0 mm.
Wind pressure is taken as 0 kPa. Affected gates carry a "wind not applicable" remark.
Used as entered for global stability; multiplied by the stated 1.3 screening factor for the wall action envelope. Confirm pressure basis and required factors for the project.
Seismic actions are taken as zero. Every affected gate is labelled "seismic not considered" and the report carries the same remark. Results do not cover seismic loading.
Seismic help — how each seismic entry is used and where to get it
Read this first. In computed mode Tankwise calculates the seismic forces from your site criteria (SDS, SD1, I, Ri, Rc) with the ACI 350.3 / Housner two-mass model for a rectangular ground-supported tank: impulsive and convective (sloshing) water, wall and roof inertia, wall-base moment and shear per metre, base shear, overturning moment and sloshing wave height, in both plan directions. It then adds them to the water, soil and wind actions in the wall and stability checks. In entered mode it only records the criteria and takes four actions that you calculate separately. Computed values are screening-level: spectral accelerations use the plateau (SDS) for the impulsive mode, which is conservative for stiff concrete tanks; vertical acceleration, dynamic soil pressure and liquefaction are not included.
1. Suggested workflow
- Choose the design basis above: computed (Tankwise calculates the forces), entered (you supply four actions from an external analysis) or not considered (state the basis; actions become zero and every affected gate is labelled).
- Get SDS, SD1 and Site Class from the project seismic criteria and the geotechnical report. NSCP 2015 §208 gives Z, Na, Nv, Ca, Cv: use the NSCP 2015 helper in the seismic panel to convert them to SDS and SD1.
- Pick I from the risk category of the tank, and Ri / Rc from ACI 350.3 for your tank type and base condition.
- Computed mode: check TL, the load factor and the strength-to-service divisor, then read the working in the Seismic Analysis card on the Results tab. Compare the sloshing wave height with your freeboard.
- Entered mode: run the seismic analysis outside the tool (impulsive + convective loads, wall inertia, dynamic soil pressure for buried tanks) and enter the four actions at the correct load level (see section 4). Re-use the same I, Ri and Rc as that analysis.
- Check that no seismic gate in the results still reads NOT EVALUATED.
2. Site criteria — drive the computed analysis (gates only in entered mode)
| Entry | Unit | Where it comes from / what to know |
|---|---|---|
| SDS | g | Design spectral acceleration at short period (the plateau). NSCP 2015 §208 follows the UBC-97 form, so SDS = 2.5·Ca (the NSCP helper does this). If your project criteria use ASCE 7 instead, SDS = (2/3)·Fa·SS. It already includes the site coefficient. Must be > 0. |
| SD1 | g | Design spectral acceleration at 1 s. From NSCP, SD1 = Cv (the helper does this); in ASCE 7 form SD1 = (2/3)·Fv·S1. Note that in Zone 4 near a fault Cv can exceed SDS; the tool handles this, but check the source. Must be > 0. |
| Site Class | A to F | From the geotechnical report (NSCP SA to SE map to Site Class A to E; SF needs a site-specific study). The tool does not guess it. Class F needs a site-specific response analysis. Use Class D by default only if the project criteria allow it where soil data is incomplete. |
| Importance factor I | – | Follows the occupancy category. NSCP Table 208-1: 1.00 for standard, special occupancy and miscellaneous structures (an ordinary domestic or rainwater cistern), 1.25 hazardous facilities, 1.50 essential facilities (e.g. a tank serving a hospital or fire-suppression supply). ASCE 7 risk categories II / III / IV correspond to 1.00 / 1.25 / 1.50. Confirm with the project criteria. |
| Impulsive Ri | – | ACI 350.3 table value for the tank type and base condition (fixed, hinged, anchored, unanchored, buried). Buried tanks have their own entry: do not reuse an above-ground value. |
| Convective Rc | – | 1.0 for the sloshing mode in ACI 350.3. Confirm against your edition and project criteria. |
| TL (computed mode) | s | Long-period transition. Used only when the sloshing period exceeds it, where Sac = 1.5·SD1·TL/Tc². Default 4 s; use the project value if given. |
| Load factor on E (computed mode) | – | Applied to the strength-level wall action together with Sd = 1.3, the same durability factor the tool applies to water and wind. Default 1.0. |
| Strength → service divisor (computed mode) | – | Converts strength-level base shear and overturning to the service level used in the stability checks. Default 1.4 (ASCE 7-10 style E). |
The code reference is Chapter 2, Section 208 of NSCP 2015 plus ACI 350.3. Verify the exact table and section numbers against your copy and the current project criteria.
3. What computed mode calculates
- Model: ACI 350.3 / Housner two-mass model for a rectangular ground-supported tank, run for motion along L and along B. The larger wall action governs.
- Impulsive: Sai = SDS·I/Ri (plateau, conservative for stiff concrete); Pi = Sai·Wi. Wall, roof (including SDL and soil cover) and base-slab inertia use the same Sai.
- Convective (sloshing): Tc from the sloshing frequency; Sac = 1.5·SD1/Tc (capped at 1.5·SDS); Pc = Sac·I·Wc/Rc.
- Wall action per metre: the water force on each loaded wall is half of Pi or Pc divided by the wall width, spread linearly over the water depth. Wall self-inertia is a uniform out-of-plane pressure. Impulsive + inertia and convective are combined by SRSS.
- Full tank wall case = hydrodynamic + wall inertia. Empty tank wall case = wall inertia only.
- Global: base shear and overturning about the underside of the base slab (SRSS of the impulsive-group and convective forces), divided by the service divisor. The empty-tank values feed the existing empty-tank sliding, overturning and bearing gates; the full-tank values feed the new full-tank seismic stability check.
- Sloshing wave height: δmax = 0.5·L·I·Sac, checked against the freeboard.
- Not included: vertical acceleration, dynamic soil pressure, roof sloshing pressure, in-plane shear of walls and roof, soil-structure interaction, liquefaction.
4. Entered mode — the four seismic actions
| Entry | Unit | Level | How the tool uses it |
|---|---|---|---|
| Factored seismic wall-base moment | kN·m/m | FACTORED | Added as entered, with no extra factor, to the factored water, soil and wind wall-base moment. The same entry feeds both the full-tank and the empty-tank wall cases. |
| Seismic wall-base shear | kN/m | FACTORED | Added as entered to the factored water, soil and wind wall shear, for the same two cases. |
| Global seismic base shear | kN | SERVICE | Added to the wind resultant in the sliding check: factor of safety = base friction ÷ (wind + this value). |
| Global seismic overturning moment | kN·m | SERVICE | Added to the wind moment in the overturning and eccentric bearing checks. Take it about the underside of the base slab. |
Mind the load level. The wall entries are strength-level, the global entries are service-level. If your analysis gives strength-level global forces, convert them with the factor your code allows before entering. Example (ASCE 7-10 basis): Estrength = 140 kN → service = 140 ÷ 1.4 = 100 kN. Entering a factored value in a service field overstates the demand; entering a service value in a factored field understates it.
- Entered mode only. Blank means not yet provided: the related gate stays NOT EVALUATED. 0 means you are stating that the action is zero, so enter it only where you can justify it.
- The wall envelope adds actions by magnitude (a conservative screen). In entered mode one wall entry serves both the full and the empty case, so enter the larger of the two governing values. Computed mode keeps the two cases separate.
5. Underground (buried) tanks
- The tool's soil pressure is static only. Seismic earth pressure is not computed in either mode. In entered mode include it in the wall moment and shear you enter. In computed mode the empty-tank wall case contains wall inertia only, so the dynamic soil increment must be added separately by the Engineer of Record.
- The governing seismic effect on buried walls is usually the dynamic lateral earth pressure increment (Mononobe-Okabe or a simplified equivalent-fluid increment), most critical for the empty tank. Hydrodynamic water pressure matters for the full or partly full tank, more so for large tanks.
- Wall and roof inertia are normally small because a buried tank moves with the surrounding soil.
- A fully buried, soil-confined tank usually does not govern in global sliding or overturning. In entered mode, if you enter 0 for the two global actions, record the reason in your calculation file. Computed mode still reports the global actions for the buried tank without crediting soil confinement.
- Liquefaction, differential settlement and flotation are separate checks. The seismic fields do not cover them.
6. When "Seismic not considered" is acceptable
Only where the governing code and the project criteria allow it, or where the seismic design is done by others. State the basis in the field provided: it prints in the gate remarks and on the report. All results then cover non-seismic load cases only, and the Engineer of Record should confirm the exclusion.
7. Quick checklist
- SDS, SD1, I, Ri, Rc, TL match the project criteria (computed mode), or I, Ri, Rc and the entered actions come from the same analysis (entered mode).
- Wall actions are factored; global actions are service. Units are per metre of wall for wall actions and for the whole tank for global actions.
- Sloshing wave height is within the freeboard, or the roof and upper wall are designed for it.
- Dynamic soil pressure is added for buried tanks.
- No seismic gate reads NOT EVALUATED, and section 3A (computed) or the entered values appear in the report.
Seismic inputs — site criteria Open seismic help
NSCP 2015 helper — get SDS and SD1 from Z, Na, Nv, Ca, Cv
Conversion used: SDS = 2.5·Ca (spectral plateau) and SD1 = Cv (the Cv/T branch), the standard equivalence between the UBC-97 spectrum used by NSCP §208 and the ASCE 7 form used by ACI 350.3. Distance must be taken from the PHIVOLCS fault map; values between listed distances are not interpolated, so choose the nearer, more severe entry. Confirm every table value against your copy of NSCP 2015.
Design-level spectral response acceleration at short periods, in units of g, for the site.
- Take it from the project seismic criteria or site hazard study (NSCP 2015 / ASCE 7 procedure); it already includes the site class coefficient.
- Used directly by the Tankwise seismic analysis in computed mode (a completeness gate only when actions are entered): it does not generate forces here.
- Must be greater than 0.
Design-level spectral response acceleration at a 1-second period, in units of g.
- Same source as SDS (site hazard study or project criteria).
- Used directly by the Tankwise seismic analysis in computed mode (a completeness gate only when actions are entered).
- Must be greater than 0. Typically SD1 is less than SDS.
Factor that raises the seismic design force for tanks whose failure has serious consequences.
- Typically 1.0, 1.25 or 1.5 depending on the use group or risk category (ACI 350.3 / ASCE 7); confirm the value your project criteria assign.
- Use the same value that was used in the separate seismic analysis.
- Must be greater than 0.
Reduces the elastic force for the impulsive (rigid-wall-with-liquid) mode.
- Depends on the tank type and base condition (fixed, hinged, anchored, unanchored); take it from the ACI 350.3 table that applies to your tank.
- Use the value used in the separate seismic analysis.
- Must be greater than 0.
Applies to the convective (sloshing) mode.
- ACI 350.3 uses 1.0 for the sloshing mode; confirm against your edition and project criteria.
- Use the value used in the separate seismic analysis.
- Must be greater than 0.
Soil profile class from the geotechnical report, A (hard rock) to F (special soils).
- Select the class stated in the approved geotechnical report; the tool does not guess it.
- Class F needs a site-specific response analysis.
- Used directly by the Tankwise seismic analysis in computed mode (a completeness gate only when actions are entered).
TL: use the project/NSCP long-period value (4 s if not given). E is the strength-level ACI 350.3 force (already reduced by Ri, Rc); the wall action is then multiplied by the load factor and by Sd = 1.3 like the other wall actions. Global base shear and overturning moment are divided by the divisor to give the service-level values used in the stability checks (1.4 for ASCE 7-10 style E).
Seismic bending moment at the base of the wall, per metre of wall width, from the separate verified analysis.
- Unit: kN·m per m. Enter it already at strength (factored) level: the tool adds it as entered, with no extra factor, to the 1.3 × 1.6 water and wind actions.
- Include impulsive, convective and wall inertia effects, and dynamic soil pressure for buried tanks, as your analysis requires.
- Enter 0 only where a zero value is justified. Blank means the gate stays NOT EVALUATED.
Seismic shear at the base of the wall, per metre of wall width, from the separate verified analysis.
- Unit: kN per m. Enter it at strength (factored) level; the tool adds it as entered to the factored water and wind shear.
- Use the same load case and basis as the wall-base moment.
- Enter 0 only where justified. Blank leaves the shear gate NOT EVALUATED.
Total horizontal seismic force acting on the whole tank, used with wind in the sliding check.
- Unit: kN. Enter it at service (unfactored) level. If your analysis gives strength-level force, convert it using the factor your code allows (for example E divided by 1.4 in ASCE 7-10) before entering.
- Compare with the base friction: sliding factor of safety = friction / (wind + this value).
- Enter 0 only where justified.
Total seismic overturning moment on the whole tank, used with wind in the overturning and eccentric bearing checks.
- Unit: kN·m. Enter it at service (unfactored) level.
- Take the moment about the underside of the base slab (including pressure effects on the base, if your analysis gives them separately).
- Use the same load case as the global base shear. Enter 0 only where justified.
Liquid-tightness, roof, and geotechnical design inputs
Provide project-specific values from the architectural/structural criteria and approved geotechnical report. No soil cohesion, passive resistance, or soil cover over the base ledge is assumed.
Vertical distance from the underside of the base slab up to the design water table.
- 0 = water table at or below the base. No uplift and no external water pressure on the walls. Use only if the site is permanently dry or drained.
- Use the highest expected (wet-season / flood) level from the geotechnical report.
- If unknown, the conservative value is ground level: Hs + base slab thickness. The wall pressure is capped at the ground surface.
Minimum acceptable ratio of friction resistance to lateral force (wind + seismic base shear). Set by the project or geotechnical report.
- Typical: 1.5 for normal loading.
- Some criteria allow about 1.1 to 1.25 for short-term wind or seismic cases.
- Must be 1.0 or more. 0 is not valid.
Minimum ratio of stabilizing moment (net empty-tank weight × half the footprint width) to overturning moment from wind and seismic.
- Typical: 1.5 for normal loading.
- Some criteria allow about 1.1 to 1.25 for short-term wind or seismic cases.
- Must be 1.0 or more. 0 is not valid.
Minimum ratio of resisting weight (empty tank, plus soil if credited) to the hydrostatic uplift on the base.
- Typical: 1.1 minimum; use about 1.2 to 1.5 where groundwater or soil weight is uncertain.
- Soil weight counts only if you tick the credit option in the underground panel.
- Must be 1.0 or more. Enter the groundwater head first, since uplift is zero when it is 0.
Real-Time Structural Geometry Render
Dynamic CAD ViewElevation Cross Section (Wall & Cover)
Plan Cross Section (Top View)
Schematics update dynamically upon input parameter changes.
Analysis Results & Verification Checks
Preliminary screening only — not a complete code-compliance or construction design check.
| Screening Check / Gate | Basis / Limitation | Demand Value | Capacity Limit | Status | Recommended Action / Adjustment |
|---|
Indicative Reinforcement Area & Spacing Estimates
Estimates use an assumed reinforcement ratio and spacing cap; they are not a verified code minimum, crack-control design, or complete reinforcement schedule.
| Structural Part | Bar Diameter (φ) | Assumed As Target (mm²/m) | Calculated Max Spacing | Design Selected Spacing | Provided As (mm²/m) | Difference from Assumed Target |
|---|
Reinforcement Detailing — Development, Laps, Hooks and Anchorage
Seismic Analysis — ACI 350.3 Impulsive & Convective (Rectangular Tank)
Housner two-mass model, both plan directions. Wall actions are per metre of wall width and feed the wall flexure and shear checks; global actions feed the stability checks. Screening level: verify against the governing code edition.
Partition Wall — Design Actions & Effect on Sloshing, Freeboard and Members
Compares the tank with and without the partition. Screening level: one-way vertical strip design of the partition, nominal ACI 350.3 compartment forces; verify before issue.
Flexural & Structural Mechanics
Soil, Serviceability & Flotation Screening
Tankwise — a product of RLN Centerline
Structural & Civil Engineering Calculations
Preliminary Water-Tank Screening Calculation Report
1. Preliminary Basis & Limitations
This tool provides simplified screening calculations against an intended reference basis of NSCP 2015 / ACI 350-06 / ACI 318-14. It includes a flexural crack-width estimate for the full-tank wall case and a two-way elastic roof-plate calculation when a roof is selected. The model is an above-ground rectangular tank; the base slab is assumed continuously supported for the average gravity-bearing screen, while conservative wall-to-wall strip checks take no soil-support credit. These calculations do not establish code compliance, crack-width control, liquid-tightness, or construction readiness. The listed checks are incomplete and require review and completion by the Engineer of Record.
Design basis used by Tankwise: strength design with load factors 1.2D + 1.6L and 1.6F (ACI 318-14 / NSCP 2015 style) multiplied by the ACI 350 environmental durability factor Sd = 1.3 for flexure and shear and 1.65 for direct tension, applied to walls, base, partition and roof alike. Sd is not reduced for the steel grade, which is conservative for Grade 40 bars. The partition is checked as a one-way vertical strip (cantilever, or propped when it carries the roof slab) with no credit for three-sided plate action, which is conservative. The load factors differ from those printed in ACI 350-06; confirm the governing edition with the reviewer.
2. Applied Loads & Material Specifications
- • Concrete Compressive Strength (f'c): -- MPa
- • Steel Yield Strength (fy): -- MPa
- • Unit Weight of Concrete: 24.0 kN/m³
- • Fluid Density (Water): 9.81 kN/m³
- • Allow. Soil Bearing Capacity (qallow): -- kPa
- • Water Depth (hw): -- m
- • Freeboard (FB): -- m
- • Partition wall: None
- • Base Projection Ledge (Lledge): -- m
- • Installation: --
- • Clear cover / wind pressure: --
- • Seismic inputs (SDS / SD1 / I / Ri / Rc / Site Class): --
- • Roof/geotechnical inputs (SDL / live / equipment / μ / groundwater / FS): --
3. Structural Verification Summary
| Criteria | Screening Basis / Limitation | Demand Value | Capacity Limit | Status | Required Action / Limitation |
|---|
3A. Seismic Analysis — ACI 350.3 Impulsive & Convective Forces
Housner two-mass model for a rectangular ground-supported tank. Strength-level E (reduced by Ri, Rc); wall actions per metre of wall width; global actions about the underside of the base slab. Screening-level calculation for engineer review.
3B. Partition Wall — Design Actions & Effect on Sloshing, Freeboard and Members
4. Individual Reinforcing Steel Bar Details & Sketches
5. Screening Conclusion — Not a Design Approval
This report is an incomplete screening calculation and must not be used as evidence of code compliance or construction readiness.
Required independent engineer review before issue
Confirm governing code editions and site criteria; validate the complete strength/service load combinations and ACI 350.3 hydrodynamic actions; verify structural analysis, member capacities, crack control, joints, anchorage, development and detailing; review geotechnical report, groundwater, bearing, settlement, sliding, overturning and uplift; resolve every FAIL and NOT EVALUATED result; then prepare and sign/seal project construction documents.
6. Engineer Review Status & Certification
| Certifying engineer -- | Licence / PRC no. -- | Checked by -- |
| Signature | Date | Seal / stamp |
Complete only after independent review. This application provides a preliminary screening calculation and does not certify the design.
Pursuant to Republic Act No. 544, as amended by Republic Act No. 1582 (the Civil Engineering Law of the Philippines), and Presidential Decree No. 1096 (the National Building Code of the Philippines) and its Implementing Rules and Regulations, all structural plans and specifications submitted to the Office of the Building Official must be prepared, signed, and sealed by a duly licensed Professional Civil Engineer."
Reinforcement detailing summary
Design aspects not evaluated by this application
The following aspects have no complete calculation in this application and are not included as pass/fail checks in the verification table. They require separate project-specific analysis and review by the Engineer of Record:
- Partition wall (if selected): plate action and in-plane shear for motion parallel to the partition, hydrodynamic pressure on a partial-height baffle (only its inertia is included), openings or doors, and joint and waterstop details are not evaluated. No sloshing reduction is credited for a partial-height baffle.
- Complete governing code load combinations, including full/empty tank conditions, pressure reversal, vertical seismic effects, and combined wind/seismic/hydraulic cases.
- Horizontal wall bending and corner moments from plate action, and the true share of water pressure carried horizontally versus by vertical cantilever action. The horizontal direct-tension check is a conservative screen that assigns the full pressure to horizontal tension at the base level.
- Seismic forces: in computed mode only the ACI 350.3 Housner-model screening forces in section 3A are included (rectangular ground-supported tank; impulsive spectrum taken at the SDS plateau; no vertical acceleration, dynamic soil pressure, roof sloshing pressure, in-plane wall/roof diaphragm shear or liquefaction); in entered mode the action values must come from a separately verified analysis.
- Restraint-, shrinkage-, and temperature-induced crack widths; joints, waterstops, construction quality, and leakage performance. The reported crack-width estimate covers flexural cracking from internal water pressure only.
- Two-way plate/soil-structure interaction, punching and local shear, wall-to-slab force transfer, construction stages, and complete crack-control design of the base slab; the shown wall-to-wall strip results are only limited screens.
- Where a roof slab is selected: openings, concentrated loads, diaphragm actions, wind uplift, restraint/fixity, long-term cracked deflection, punching/local bearing, and support-force transfer. The calculated two-way plate model assumes a solid, uniformly loaded slab simply supported on all four wall edges. Not applicable to the selected open-top configuration.
- Geotechnical settlement, liquefaction, slope/global stability, soil-structure interaction, and project-specific bearing-resistance criteria.
- Underground installation: seismic and compaction-induced earth pressures, wall–roof frame action, soil-structure interaction, drainage/waterproofing, construction-stage backfilling (differential backfill), and long-term groundwater variation. External pressures use the simplified K·(γz+q)+γw·hw model; the roof soil cover load uses the entered total unit weight.
- Bar scheduling and bending, openings and penetrations, joint layout and waterstop locations, durability design, and construction-document coordination. The development length, lap, hook and anchorage values shown are screening values and must be verified against the governing code edition.